02 – Test Parameters per OCP UQD Specification v2.0.0

Source: Open Compute Project – Cooling Environments: Cold Plate Sub-Project, Design Specification Universal Quick Disconnect (UQD) v2.0.0, effective 2026-09-22. Products: UQD02, UQD04, UQD06, UQD08 (handmate) · UQDB02, UQDB04, UQDB06, UQDB08 (blindmate) Units: mm unless stated otherwise. bar(g)/psi(g) = gauge pressure.


1. General test requirements

Parameter Value Ref
Medium (system type) Non-flammable single-phase, water/glycol §5
Min. samples per test (verification) 5 (ISO 18869) §9
Min. samples per test (cross-verification) 3 §10
Instrument accuracy Per ISO 18869:2017 §6.3 §9
Helium leak test Per ASTM E493 §9
QD Property Tests (9.1.x) May run in parallel on different samples §9
Thermal/Mechanical Tests (9.2.x) Run sequentially on the same samples §9
Cross-verification At least 3 other suppliers; tests 9.1.2, 9.1.3, 9.1.4, 9.1.5 §10
Marking UQDxx v2 / UQDBxx v2; handmate: colour identification red + blue (minimum) §11

Test sequence 9.2 (same sample set)

  1. Helium leak test (optional screening)
  2. Non-Op temperature cycling (9.2.1)
  3. Helium leak test (optional screening)
  4. Op temperature cycling (9.2.2)
  5. Hydrostatic pressure test (9.2.4)
  6. Mechanical cycling (9.2.3)
  7. Hydrostatic pressure test (9.2.4)

2. Performance requirements (Table 6)

Parameter Unit 02 04 06 08 Test
Max operating pressure bar(g) / psi(g) 6.89 / 100 6.89 / 100 6.89 / 100 6.89 / 100 9.1.1
Min burst pressure bar(g) / psi(g) 20.68 / 300 20.68 / 300 20.68 / 300 20.68 / 300 9.1.1
Rated flow L/min 2.27 6.44 11.36 17.79 9.1.4, 9.1.5
Rated flow GPM 0.6 1.7 3.0 4.7 9.1.4, 9.1.5
Min Cv – 0.30 1.1 2.2 3.6 9.1.4
Max Cv – 0.43 1.6 3.3 5.6 9.1.4
Max coupling force @ 0 psi ¹ N 55.0 65.0 90.0 135.0 9.1.3
Max coupling force @ 0 psi ¹ lbf 12 15 20 30 9.1.3
Force/pressure scaling factor N/bar 3.47 9.62 16.06 24.00 9.1.3
Force/pressure scaling factor lbf/psi 0.054 0.164 0.274 0.409 9.1.3
Min number of coupling cycles # 5000 5000 5000 5000 9.2.3
Max fluid loss per cycle mL 0.02 0.03 0.04 0.07 9.1.2
Temp. non-operating/shipping °C −40 … +70 ← ← ← 9.2.1
Temp. operating °C +5 … +65 ← ← ← 9.2.2
Storage life (from T0 = date of manufacture) years 5 5 5 5 –
Service life in operation (after storage) years 10 10 10 10 –

¹ Applies to UQDB only (valve force). For handmate UQD the latch mechanism is expected to give a marginally higher force.

Pressure drop equation: ΔP(Q) = A·Q² + B·Q (ΔP in psi, Q in L/min). Min/max for A, B are not yet defined in v2.0.0.

Max flow (recommendation): volume flow corresponding to 5 m/s through the smallest cross-section area – contact the QD supplier.

2.1 Calculated max coupling forces at test pressure (UQDB)

F_max = F(0 psi) + p · scaling factor

Size 0 bar(g) 2.76 bar(g) 6.89 bar(g)
UQDB02 55.0 N 64.6 N 78.9 N
UQDB04 65.0 N 91.6 N 131.3 N
UQDB06 90.0 N 134.3 N 200.7 N
UQDB08 135.0 N 201.2 N 300.4 N

2.2 Calculated flows for the tests

Size 25 % (L/min) 100 % (L/min) 150 % (L/min) 200 % – Seal washout (L/min) 200 % (GPM)
02 0.57 2.27 3.41 4.54 1.2
04 1.61 6.44 9.66 12.88 3.4
06 2.84 11.36 17.04 22.72 6.0
08 4.45 17.79 26.69 35.58 9.4

3. Test parameters per test

9.1.1 Burst Pressure

Parameter Value
Object Plug, socket and mated coupling
Position Fully mated (UQD only) and unmated (all plugs/sockets)
Test pressure To failure, or 3 × min. proof pressure – whichever is lower
Pressure rise rate Per ISO 18869
Acceptance Burst pressure > 20.68 bar(g) / 300 psi(g)
Result P/F per sample (1–5) for Plug / Socket / Mated

⚠️ "Minimum proof pressure" is not defined in the specification – determine the value (e.g. from ISO 18869 or customer requirement) before the test.

9.1.2 Fluid Loss

Parameter Value
Method ISO 18869 §12
Test medium Water
Acceptance (mL/cycle) 02: ≤ 0.02 · 04: ≤ 0.03 · 06: ≤ 0.04 · 08: ≤ 0.07
Record Liquid level before/after (mL), number of couplings, loss per cycle, mean over samples

9.1.3 Force to Connect

Parameter Value
Method ISO 18869 §7
Repetitions 5 per sample; max force per test, the mean of all maxima over all samples is reported
Temperature Room temperature
Test pressure 0 / 2.76 / 6.89 bar(g) (0 / 40 / 100 psi(g)), pressure on both plug and socket
Medium Air or water, pressurized
Connection speed 40 ± 10 mm/s
Alignment Fully radially and angularly aligned (unless stated otherwise)
Lubrication No extra lubrication or alignment beyond normal use
Specific to UQDB Test at max radial misalignment (SA = 1.00 +0.30/−0.00 mm), reset after each cycle
Acceptance See table 2.1 (UQDB)

9.1.4 Pressure Drop

Parameter Value
Method ISO 18869 §13 (with deviations below)
Temperature 25 ± 5 °C
Medium Water
Flows At least 6 flows between 25 % and 150 % of rated flow, incl. 100 %
Flow direction Both: S→P and P→S
Samples n = 5 minimum, mean per direction
UQDB & Hybrid Fully mated, hard-stop
Tare (§13.3) Remove the coupling, connect hoses with a tare adapter; same hose/fittings between the pressure taps in test and tare
Net pressure drop (§13.5) Pressure drop test − pressure drop tare
Report Curve fit ΔP = A·Q² + B·Q (psi, L/min), ΔP at 100 % and 150 %, A, B, min Cv
Cv formula Cv = Q · √(SG / ΔP), Q in GPM, ΔP in psi
Acceptance Cv at rated flow within [Min Cv, Max Cv] per Table 6

Straight pipe lengths (ISO 18869 Fig. 13), minimum: | Section | Length | |---|---| | L1 | 10 × inside diameter | | L2 | 5 × inside diameter | | L3 | Length of the coupling incl. end fittings | | L4 | 10 × inside diameter | | L5 | 5 × inside diameter |

Hose/pipe ID for the test (= hosebarb size in Table 5, ±10 %): | Size | Nominal ID | ID range (mm) | L1/L4 min (mm) | L2/L5 min (mm) | |---|---|---|---|---| | 02 | 1/4" = 6.35 mm | 5.72 – 6.99 | 63.5 | 31.8 | | 04 | 3/8" = 9.525 mm | 8.57 – 10.48 | 95.3 | 47.6 | | 06 | 1/2" = 12.70 mm | 11.43 – 13.97 | 127.0 | 63.5 | | 08 | 5/8" = 15.875 mm | 14.29 – 17.46 | 158.8 | 79.4 |

Adapters ISO 11926-3 male stud → hosebarb (example in spec): | End | ID (mm) | Tol. | Length (mm) | Tol. | |---|---|---|---|---| | 11926 7/16 | 4.4 | ±0.08 | 9.1 | ±0.2 | | 1/4 HB | 4.4 | ±0.08 | 20.5 | REF | | 11926 9/16 | 7.5 | ±0.1 | 10 | ±0.2 | | 3/8 HB | 7.5 | ±0.1 | 24.1 | REF | | 11926 3/4 | 10 | ±0.1 | 11.1 | ±0.2 | | 1/2 HB | 10 | ±0.1 | 28 | REF | | 11926 7/8 | 12.5 | ±0.1 | 12.7 | ±0.2 | | 5/8 HB | 12.5 | ±0.1 | 38 | REF | | 11926 1-1/16 | 15.5 | ±0.12 | 15.1 | ±0.2 | | 3/4 HB | 15.5 | ±0.12 | 38 | REF |

Common: stud length 9.5 mm [0.38"], Ø per SAE J1926-3 / ISO 11926-3.

Tare adapter (straight, thread 1 – thread 2): | Coupling | Thread 1 | Diameter D (mm) | Length L (mm) | Thread 2 | Length L2 (mm) | |---|---|---|---|---|---| | UQDB02/UQDH02 | 7/16-20 | 9.88 ± 0.15 | 96 ± 5 | 9/16-18 | 14.5 ± 0.5 | | UQDB04/UQDH04 | 9/16-18 | 12.92 ± 0.17 | 112 ± 5 | 3/4-16 | 16 ± 0.5 | | UQDB06/UQDH06 | 3/4-16 | 17.5 ± 0.18 | 124 ± 5 | 7/8-14 | 18 ± 0.5 | | UQDB08/UQDH08 | 7/8-14 | 20.48 ± 0.21 | 139 ± 5 | 1-1/16-12 | 20.5 ± 0.5 |

Threads per SAE J1926-1 / ISO 11926-1.

9.1.5 Seal Washout (closed loop)

Parameter Value
Number of cycles 20 per flow direction (P→S and S→P)
Connection speed 40 ± 10 mm/s
Flow 2 × rated flow (see table 2.2)
Temperature 60 °C
Pressure 6.9 bar(g) / 100 psi(g) operating (excl. transient spike)
Max pressure spike at disconnect ≤ 30 psi (2.07 bar) above pressure before disconnect
Medium Water or PG25
Latch mechanism (handmate) May be removed/bypassed
Pipe length L (WHA ↔ QD) < 5 × ID
Acceptance No leakage, no seal washout

Set-up: Accumulator (air, valve A), circulation pump with bypass (valve B), pressure gauge C (upstream) and D (downstream), WHA on both sides of the QD, flow meter (LPM). Procedure: Set the flow with the coupling mated → stop the pump, disconnect → start the pump → pressurize via A to max operating pressure at C → stop the pump → connect → check flow → run cycles → change flow direction and repeat.

9.2.1 Non-Operational (Shipping) Temperature Cycling

Parameter Value
Position Fully mated (UQD/UQDB) and unmated (plug/socket); mated: connect the counterpart and plug the end
Set-up QD in an all-metal enclosure, total volume ≤ 0.5 L (as small as possible)
Temperature −40 °C for 72 h, +70 °C for 72 h, back to room temp.
Transition rate 5 – 10 °C/min
Medium Air, 28 – 30 psi(g) (≈ 1.93 – 2.07 bar(g))
Pressurization / reading At room temperature before and after
Specific to UQDB Fully mated, hard-stop
Helium leak test Optional before and after (ASTM E493)
Acceptance Pressure drop per QD ≤ 1 % of the pressure at T0 (at 30 psi: ≤ 0.3 psi/QD)

Example: 30 → 28 psi with 10 QDs = 0.2 psi/QD < 0.3 psi → pass.

9.2.2 Operational Temperature Cycling

Parameter Value
Position Mated at nominal engagement (UQD/UQDB/Hybrid) and unmated (plug/socket) – two populations or the same in series
Temperature +5 °C for 72 h, +65 °C for 72 h, back to room temp.
Transition rate 5 – 10 °C/min
Pressure 6.9 bar(g) / 100 psi(g) at test temperature
Medium Water or PG25 (compensate for evaporation)
Acceptance No visible leakage; followed by hydrostatic test 9.2.4

9.2.3 Mechanical Cycling

Parameter Value
Number of cycles 5000
Connection speed 40 ± 10 mm/s
Temperature Normal lab environment
Pressure 2.75 bar(g) / 40 psi(g)
Medium Water or PG25
UQD Latch engaged every cycle; on-axis
Hybrid On-axis; floating mechanism not needed but compliance must exist in the fixture
UQDB Cycled with SA offset (1.00 mm radial)
Acceptance No visible leakage; followed by hydrostatic test 9.2.4

9.2.4 Hydrostatic Pressure Test

Parameter Value
Object Plug, socket and/or mated coupling per the preceding test
Preparation Bleed the system
Pressure 6.9 bar(g) / 100 psi(g)
Hold time ≥ 3 min
Unmated Pressure in the direction that tends to close the valve
Mated Ensure 6.9 bar(g) internally; connect the counterpart and plug the end
Temperature Normal lab environment
Medium Water or PG25
Acceptance No visible leakage

4. Mated lengths (Figure 4, panel-to-panel, excl. termination)

Size Hybrid (UQD plug + UQDB socket) MIN / NOM / MAX UQDB MIN / NOM / MAX
02 35.85 / 36.30 / 36.75 35.6 / 36.1 / 36.6
04 43.6 / 44.1 / 44.5 43.8 / 44.3 / 44.8
06 47.1 / 47.6 / 48.0 47.1 / 47.6 / 48.1
08 51.1 / 51.6 / 52.0 50.9 / 51.4 / 51.9

Hard-stop: UQDB = flat faces against each other; Hybrid = the socket cone against the tangent diameter on the plug flange. Handmate: socket length is the max keep-in (DD), the plug position varies with the latch mechanism.


5. Dimensions

5.1 UQD Socket (Table 1)

Dim Tol. UQD02 UQD04 UQD06 UQD08
A MIN 11.25 15.65 18.85 22.05
B (sealing surface) ±0.025 6.71 11.15 14.38 17.56
C ±0.025 / [MIN, MAX] 3.63 7.14 [9.45, 9.65] [10.73, 11.07]
E MIN – MAX 12.8 – 13.7 16.6 – 18.1 17.3 – 18.8 18.5 – 20.0
F ±0.10 3.3 4.7 5.4 6.6
S max (valve stroke) REF 8.0 11.7 14.5 17.3
CC (Ø keep-in) MAX 21.0 26.0 30.0 37.0
DD (length keep-in) MAX 50.0 60.0 65.0 75.0
Entry chamfer angle 35° ± 0.5° ← ← ←

Note: Sealing surface B is machined to ≤ 32 Ra. Asymmetric latch mechanisms may exceed CC.

5.2 UQD Plug (Table 2)

Dim Tol. UQD02 UQD04 UQD06 UQD08
G ±0.025 11.0 15.4 18.6 21.8
H (sealing surface) ±0.025 6.65 11.07 14.30 17.48
J MIN 21.0 29.0 32.5 36.5
L ±0.025 3.73 7.24 9.75 11.17
M MIN – MAX 2.4 – 3.0 3.0 – 3.8 3.5 – 4.8 3.8 – 5.8
N ±0.1 15.5 21.5 25.0 29.0
P ±0.06 14.8 20.7 24.2 28.2
Q ±0.3 19.4 26.5 30.0 34.0
R MAX 6.8 11.2 14.2 17.4
AA (TSC) ±0.10 14.10 19.20 22.67 26.69
BB ±0.10 27.0 35.4 38.9 42.9
GG MAX 16.5 19.8 25.5 30.0
HH ±0.10 0.50 0.85 0.85 0.85
JJ ±1.0° 15° 10° 10° 10°

Detail A (latch surfaces): 20° ± 0.5°, 45° ± 0.5°, 35° ± 0.5°, R1.0 ± 0.10, R0.2 ± 0.10, R0.2–0.3. Detail B (tip): R0.3 min or equivalent chamfer, 2× R0.4 ± 0.10. Sealing surface H ≤ 32 Ra.

5.3 UQDB Socket (Table 3)

Dim Tol. UQDB02 UQDB04 UQDB06 UQDB08
B (sealing surface) ±0.025 6.71 11.15 14.38 17.56
C ±0.025 / [MIN, MAX] 3.63 7.14 [9.45, 9.65] [10.73, 11.07]
T (TSC) REF 4.81 5.20 4.95 4.76
U (TSC) ±0.1 11.2 16.0 19.0 22.0
V ±0.3 7.11 8.90 9.35 10.36
FF ±0.1 23.62 28.50 31.75 35.56
KK MIN 15.5 19.5 24.5 26.5
MM ±0.15 18.0 22.9 26.1 29.9
NN ±0.2 15.2 20.0 25.2 27.5
PP MIN 5.3 6.7 8.3 9.0
QQ ±0.15 17.5 22.3 27.5 29.8
RR ±0.15 17.5 22.3 27.5 33.0
Cone angle 25.0° ± 0.5° ← ← ←

Detail C: 2.65 ± 0.1, (1.15), 4× R0.2 ± 0.1. Other: R0.2 min, R0.2 ± 0.10, 1.5 min. Sealing surface ≤ 32 Ra.

5.4 UQDB Plug (Table 4)

Dim Tol. UQDB02 UQDB04 UQDB06 UQDB08
H (sealing surface) ±0.025 6.65 11.07 14.30 17.48
K ±0.3 11.0 16.1 19.6 23.6
L ±0.025 3.73 7.24 9.75 11.17
M MIN – MAX 2.4 – 3.0 3.0 – 3.8 3.5 – 4.8 3.8 – 5.8
X ±0.1 27.0 35.4 38.9 42.9
Y ±0.3 14.50 19.60 23.10 27.10
W ±0.15 21.4 25.4 28.4 31.4
SA (radial self-alignment) +0.30 / −0.00 1.00 1.00 1.00 1.00
HH ±0.10 0.50 0.85 0.85 0.85
JJ ±1.0° 15° 10° 10° 10°

Cone angle 150° min. Keep-in zone bounded by Y, K and the min angle.


6. Terminations (Table 5)

Plug – UQD & UQDB (stud end ISO 11926-3)

Size Stud Thread Hex UQD Hex UQDB Torque
02 ORB-04 7/16-20 UNF-2A 14 mm 19 mm 9 Nm
04 ORB-06 9/16-18 UNF-2A 17 mm 24 mm 15 Nm
06 ORB-08 3/4-16 UNF-2A 22 mm 27 mm 25 Nm
08 ORB-10 7/8-14 UNF-2A 27 mm 30 mm 30 Nm

Socket – UQDB (stud end ISO 11926-3)

Size Stud Thread Hex Torque
02 ORB-06 9/16-18 UNF-2A 16 mm 15 Nm
04 ORB-08 3/4-16 UNF-2A 20 mm 25 Nm
06 ORB-10 7/8-14 UNF-2A 25 mm 30 Nm
08 ORB-12 1-1/16-12 UN-2A 27 mm 48 Nm

Socket – UQD (hosebarb, push-lock, reinforced EPDM hose)

Size 02 04 06 08
Hosebarb 1/4" 3/8" 1/2" 5/8"

Receiving port: ISO 11926-1. Torques are recommended (depend on material, lubrication etc.).


7. Materials (Table 8)

Area Material
UQD/UQDB plug – outer tip/shaft SUS 303 / 304 / 304L / 316 / 316L
UQD/UQDB cone and guide area SUS 303 / 304 / 304L / 316 / 316L

Wetted materials shall be compatible with the OCP guidelines for water-based and PG-based coolants respectively.


8. Visual inspection (Appendix 15.2, recommendation)

Attribute Acceptance Zone
Surface defects ≤ 0.3 mm² 1, 2, 4a, 4b, 7
Surface defects ≤ 1.0 mm² 3, 4, 5, 6
Machining marks OK within Ra requirement All
Chips/burrs None (loose or attached) All
Foreign material/corrosion None (passivation yellowing OK) All
Thread profile Check with thread gauge or mating port 1, 7

Inspection: 360° rotation, magnification recommended, illumination ~700–1200 lux, TAPPI/ANSI T 564 for size assessment, loose particles may be blown off with filtered compressed air.


9. Open points / ambiguities in the specification

  • Burst 9.1.1: "minimum proof pressure" has no definition – needs to be determined.
  • Hybrid configuration (UQD plug + UQDB socket) is included in 9.2.2/9.2.3 and the mated lengths – decide whether it is to be tested in addition to the UQD and UQDB pairs.
  • Pressure drop coefficients A, B: min/max not defined in v2.0.0 – reporting only.
  • Force/pressure scaling factor: N/bar and lbf/psi in Table 6 do not agree for 04–08 (see 04-Backlog ER-001). Table 2.1 uses N/bar.
  • Test template 15.3.3 wrongly labels operational cycling "Subtest 9.2.1" – should be 9.2.2.
  • Coupling force requirement in Table 6 formally applies to UQDB only; no limit exists for UQD.